NEC Substitution Chart

Communication wire and cable for premise installation in accordance with Article 800, and other applicable parts of the National Electrical Code (NEC) latest issue.

Fire Resistance Level
Test Requirement
NEC Article
800
725
760
Plenum Cables
(Highest)
UL910 (Steiner Tunnel)
CSA-FT6 (Steiner Tunnel)
MPP
CMP
CL3P
CL2P
FPLP
Riser Cables
Multiple Floors
UL-1666 (Vertical Shaft)
CSA-FT4 (Vertical Tray)
MPR
CMR
CL3R
CL2R
FPLR
General Purpose Cables UL-1581 (Vertical Tray)
MP CM
CL3
FPL
Residential Cables
(Lowest) Restricted Use
CSA-FT4 (Vertical Tray)
UL-1581 VW-1
CMX

CL2
CL3X
 

Cables with a higher resistance level may be substituted for those with a lower fire resistance level.

Non-fire rated outside plant telephone cables may not run outside of a rigid metal conduit more than 50 feet from the point of entrance into a building.

Cables rated CMG or CM may be used in runs penetrating one floor. (NEC 800-53)


Type
Decription
CM Communications Wires and Cables
CL2 and CL3 Class2 and Class 3
Remote-Control, Signaling, and Power-Limited Cables
FPL
Power-Limited
Fire Alarm Cables
MP Multipurpose Cables
PLTC Power-Limited Tray Cables

NEC Substitution Chart